No. :P501,P502
- Type: Single Band, Double Band, Triple Band
- Dimension Range from DN50 to DN600
- Length: 150mm-600mm
- PN16 for DN50-DN150; PN10 for DN200-DN300; PN6 for above DN300
Material and Relevant Standards:
Main Parts:
- Body, Bridge Plate,Lockable Plate, Bolts, Nuts.Washerare
all stainless steel AISI304(A2).
Gasket
- EPDM for normal application, NBR, SILICONE, VITON foroption.
- EPDM to BS EN681-1/ NBR to EN682
- Our rubber had approved by WRAS(UK),
any certificate request pis feel free to contact with Hiwa directly.
Lug
- Ductile Iron Lugs to GGG50 FBE Coated
P501
O.D Range | Pressure(Bar) | No. of Band | O.D Range | Pressure(PN) | No. of Band | Length(mm) | ||||
in | mm | Water | Gas | in | mm | Water | Gas | |||
2.32-2.64 | 59-67 | 16 | 5 | 1 | 7.60-7.99 | 193-203 | 16 | 4 | 1 | 150-600 |
2.56-2.87 | 65-73 | 16 | 5 | 1 | 7.95-8.35 | 202-212 | 16 | 4 | 1 | 150-600 |
2.72-2.99 | 69-76 | 16 | 5 | 1 | 8.58-8.98 | 218-228 | 16 | 4 | 1 | 150-600 |
2.95-3.27 | 75-83 | 16 | 5 | 1 | 8.74-9.17 | 222-223 | 16 | 4 | 1 | 150-600 |
3.39-3.70 | 86-94 | 16 | 5 | 1 | 9.02-9.41 | 229-239 | 10 | 3 | 1 | 150-600 |
3.46-3.86 | 88-98 | 16 | 5 | 1 | 9.29-9.69 | 236-246 | 10 | 3 | 1 | 150-600 |
3.58-3.86 | 91-98 | 16 | 5 | 1 | 9.76-10.16 | 248-258 | 10 | 3 | 1 | 150-600 |
3.70-4.02 | 94-102 | 16 | 5 | 1 | 9.84-10.24 | 250-260 | 10 | 3 | 1 | 150-600 |
4.25-4.65 | 108-118 | 16 | 4 | 1 | 9.92-10.35 | 252-263 | 10 | 3 | 1 | 150-600 |
4.45-4.76 | 113-121 | 16 | 4 | 1 | 10.28-10.67 | 261-271 | 10 | 3 | 1 | 150-600 |
4.76-5.16 | 121-131 | 16 | 4 | 1 | 10.67-11.06 | 271-281 | 10 | 3 | 1 | 150-600 |
4.96-5.35 | 126-136 | 16 | 4 | 1 | 11.02-11.46 | 280-291 | 10 | 3 | 1 | 150-600 |
5.20-5.59 | 132-142 | 16 | 4 | 1 | 11.34-11.73 | 288-298 | 10 | 3 | 1 | 150-600 |
5.71-6.10 | 145-155 | 16 | 4 | 1 | 11.73-12.17 | 298-309 | 10 | 3 | 1 | 150-600 |
5.94-6.34 | 151-161 | 16 | 4 | 1 | 11.81-12.20 | 300-310 | 10 | 3 | 1 | 150-600 |
6.26-6.69 | 159-170 | 16 | 4 | 1 | 11.97-12.36 | 304-314 | 10 | 3 | 1 | 150-600 |
6.54-6.97 | 166-177 | 16 | 4 | 1 | 12.64-13.03 | 321-331 | 10 | 3 | 1 | 150-600 |
6.69-7.09 | 170-180 | 16 | 4 | 1 | 13.11-13.50 | 333-343 | 10 | 3 | 1 | 150-600 |
6.85-7.24 | 174-184 | 16 | 4 | 1 | 13.39-13.82 | 340-351 | 10 | 3 | 1 | 150-600 |
7.05-7.44 | 179-189 | 16 | 4 | 1 | 13.70-14.09 | 348-358 | 10 | 3 | 1 | 150-600 |
7.44-7.83 | 189-199 | 16 | 4 | 1 | 14.02-14.41 | 356-366 | 10 | 3 | 1 | 150-600 |
P502
O.D Range | Pressure(Bar) | No. of Band | O.D Range | Pressure(PN) | No. of Band | Length(mm) | ||||
in | mm | Water | Gas | in | mm | Water | Gas | |||
4.45-5.24 | 113-133 | 16 | 4 | 2 | 14.37-15.12 | 365-384 | 10 | 3 | 2 | 150-600 |
4.72-5.55 | 120-141 | 16 | 4 | 2 | 15.08-15.83 | 383-402 | 10 | 3 | 2 | 150-600 |
6.61-7.40 | 168-188 | 16 | 4 | 2 | 15.91-16.65 | 404-423 | 10 | 3 | 2 | 150-600 |
6.85-7.64 | 174-194 | 16 | 4 | 2 | 16.57-17.32 | 421-440 | 10 | 3 | 2 | 150-600 |
8.62-9.41 | 219-239 | 16 | 4 | 2 | 17.17-17.91 | 436-455 | 10 | 3 | 2 | 150-600 |
8.98-9.80 | 228-249 | 16 | 4 | 2 | 17.83-18.58 | 453-472 | 10 | 3 | 2 | 150-600 |
10.75-11.54 | 273-293 | 16 | 4 | 2 | 18.46-19.21 | 469-488 | 10 | 3 | 2 | 150-600 |
11.10-11.89 | 282-302 | 10 | 3 | 2 | 19.21-19.96 | 488-507 | 10 | 3 | 2 | 150-600 |
11.61-12.40 | 295-315 | 10 | 3 | 2 | 19.88-20.67 | 505-525 | 10 | 3 | 2 | 150-600 |
12.76-13.54 | 324-344 | 10 | 3 | 2 | 20.71-21.46 | 526-545 | 10 | 3 | 2 | 150-600 |
13.19-13.98 | 335-355 | 10 | 3 | 2 | 21.54-22.28 | 547-566 | 10 | 3 | 2 | 150-600 |
13.66-14.45 | 347-367 | 10 | 3 | 2 | 22.13-22.87 | 562-581 | 6 | 3 | 2 | 150-600 |
14.06-14.80 | 357-376 | 10 | 3 | 2 | 22.91-23.66 | 582-601 | 6 | 3 | 2 | 150-600 |
Installation Length Selection:
- For normal pipes, the installation length of the repair clamp should be the size of the damaged area(B) plus the pipe outside diameter( C ), thats B+C.
- For PE/PVC pipes, the installation length of the repair clamp should be add 50% of the above value to the sum.